The aim of emergency lighting is to enable people to exit a room or
building safely. It must also ensure that fire fighting and safety equipment can be easily found and operated when needed. This equipment includes (but not exclusively):
Lighting is required near each first aid kit, near each alarm and piece of fire fighting equipment, as well as each sign indicating a fire alarm system. In accordance with EN 1838, "near" generally means a distance of no greater than 2 metres, measured horizontally (this corresponds with distance a in the diagram below). The required level of illuminance on the equipment is 5 lx measured vertically – i.e. perpendicular to the usual horizontal illuminance measurements on one level. In comparison to the escape route requirement for 1 lx horizontally, different requirements apply in this situation for the light distribution from the safety luminaires, due to the flatter light angle of incidence.
Your search "" did not match any documents or products.
| 40071356552 | GuideLed SL 13822.2 1-8h/D CGLine+, square surface mounting luminaire, with symmetric optics, 4000 K |
| 40071356553 | GuideLed SL 13812.2 1-8h/D CGLine+, square surface mounting luminaire, with asymmetric optics, 4000 K |
| 40071356554 | GuideLed SL 13852.2 1-8h/D CGLine+, square surface mounting luminaire, with asymmetric optics for 5 lx vertical illuminance, 4000 K |
| 40071356555 | GuideLed SL 13821.2 1-8h/D CGLine+, round recessed mounting luminaire, with symmetric optics, 4000 K |
| 40071356556 | GuideLed SL 13811.2 1-8h/D CGLine+, round recessed mounting luminaire, with asymmetric optics, 4000 K |
| 40071356557 | GuideLed SL 13851.2 1-8h/D CGLine+, round recessed mounting luminaire, with asymmetric optics for 5 lx vertical illuminance, 4000 K |
| Luminous flux at end of rated operating time | 100% @ 1h, 80% @ 2h, 55% @ 3h, 23% @ 8h |
| Illumination in mains mode | 10% or 100% setting via switch, and possible additional levels adjustable via test button (30%, 70%, 100%) |
| Operation | Maintained / Non-Maintained (via switched input L‘) |
| Testing system | Automatic Test in compliance with EN 62034 Central monitoring via CGLine+ system |
| Type of mounting | Surface or recessed mounting |
| Housing material | Polycarbonate, aluminium heatsink |
| Housing color | White RAL 9016 |
| Degree of protection | IP40 / IK03 (IP41 for recessed) |
| Terminals | Through-wiring from mains (L, L’, N, PE) with up to 2.5 mm² CGLine+ bus through-wiring with up to 1.5 mm² |
| Connection voltage | 220 - 240 V AC, 50/60 Hz |
| Permissable ambient temperature | 5°C to 45°C (NM), 0°C to 45°C (M), 35°C max. for 10 years lifetime |
| Battery | LiFePO4 3.2 V / 3 Ah (Spare part: FT-BATLL3) |
| Light source | 1 x 2 W LED, 4000 K, CRI ≥70, Lifespan 100 000h |